AZM 161 BZ ST1-AS RAP Schmersal Safety Switch Interlocks
Part#:AZM 161 BZ ST1-AS RAP
Manufacturer:Schmersal
Alt. Part#:101209116
Product Lifecycle:Active
Get a quick Quote!
AS interface safety at work; Safety switchgear; Solenoid supply 24 VDC (Aux); Combined monitoring of actuator and solenoid interlock; Manual release; Solenoid interlock; Thermoplastic enclosure; High holding force 2000; 130 mm x 90 mm x 30 mm; Interlock w
About the manufacturer: Schmersal is one of the manufacturers that offers Safety Switch Interlocks that you can order at Applied Automation site. Schmersal produces a wide range of high-quality switchgears specifically engineered to protect machinery and facilities in industrial automation and the elevator industry.
Check out the AZM 161 BZ ST1-AS RAP Schmersal price in the box on the right side or send a quick quote.
Product Details
- Rated operating voltage 24 VDC -15% / +10% (stabilised PELV)
- Note (AS-i Parameter bits) Set the parameter outputs to "1111" (0xF)
- AS-i Parameter bits, P2 Magnet voltage in tolerance range
- Operating current 500 mA
- Note (AS-i Input module address) Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
- AS-i Parameter bits, P3 Error message - locking/unlocking of the solenoid interlock blocked
- AS-i Outputs, DO 2 No Function
- AS-i Outputs, DO 3 No Function
- AS-i Input module address 0
- AS-i, ID-Code2 0xE
- AS-i Outputs, DO 1 No Function
- AS-i Outputs, DO 0 Solenoid control
- AS-i Input, Channel 2 Data bits DI 2 / DI 3 = dynamic code transmission
- AS-i Input, Channel 1 Data bits DI 0 / DI 1 = dynamic code transmission
- AS-i Parameter bits, P0 Actuator detected
- AS-i Parameter bits, P1 Solenoid interlock locked
- AS-i, ID-Code 0xB
- AS-i Version V 2.1
- AS-i, ID-Code1 0xF
- AS-i, IO-Code 0x7
- AS-i Profile S-7.B.F.E
- AS-i Specification Safety-Slave
- AS-i Current consumption, maximum 100 mA
- Note (AS-i Operating voltage) Protection against polarity reversal
- AS-i Operating voltage, minimum 26.5 VDC
- AS-i Operating voltage AS-i maximum 31.6 VDC
- Switching frequency 1,000 /h
- Degree of pollution to VDE 0100 3
- Overvoltage category III
- Rated impulse withstand voltage Uimp 0.8 kV
- Protection rating II
- Rated insulation voltage Ui 32 VDC
- Restistance to shock 30 g / 11 ms
- Resistance to vibrations to EN 60068-2-6 10 Hz ... 150 Hz, amplitude 0.35 mm
- Note (Relative humidity) non-condensing, non-icing
- Relative humidity, maximum 95 %
- Storage and transport temperature, maximum +85 °C
- Ambient temperature, maximum +60 °C
- Storage and transport temperature, minimum -25 °C
- Relative humidity, minimum 30 %
- Ambient temperature, minimum -25 °C
- Degree of protection IP67 to EN 60529
- Height of sensor 90 mm
- Width of sensor 130 mm
- Terminal Connector Connector plug M12, 4-pole, (A-coding)
- Length of sensor 30 mm
- Clamping force 2,000 N
- Connector position Bottom
- Actuating speed, maximum 2 m/s
- Latching force 30 N
- Actuating play in direction of actuation 5.5 mm
- Mechanical life, minimum 1,000,000 Operations
- Number of actuating directions 3
- Manual release Yes
- Enclosure material Plastic, glass-fibre reinforced thermoplastic, self-extinguishing
- Power to lock Yes
- Integral System Diagnostics, status Yes
- Reaction time, maximum 100 ms
- Actuator and interlock combined monitored Yes
- Gross weight 451 g
- Standards IEC 61508, EN 60947-5-1, EN 62026-2
- Active principle electromechanical
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Related documents AZM 161 BZ ST1-AS RAP Specs
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
We deliver nationwide and international
Secure Payment Processing
with money back guarantee
Warranty
Manufacturer warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
What can I help you find today?